Продвижение инициативы «Один пояс, один путь», снижение регулятивного давления на правительство, экономия операционных расходов предприятий и содействие международной торговле.
Cummins diesel generator sets adopt Cummins' globally unified design, production, and testing standards, providing customers with reliable and integrated one - stop power generation systems, which perform excellently in normal, standby, and continuous operation.
Comply with ISO8528 - 2005 and GB/T2820 - 2009 《Reciprocating Internal Combustion Engine - Driven Alternating - Current Generating Sets》 standards.
The design and manufacturing units of the generator sets have all passed ISO9001 or ISO9002 certification.
Cummins provides a 1 - year or 1000 - hour (whichever comes first) quality guarantee for the generator sets and is responsible for the maintenance of the generator sets, including the engine, generator, and control system.
The professional service network across the country provides customers with 24 - hour after - sales service and technical support.
Leading design and manufacturing: Advanced design, sophisticated manufacturing technology, reliable and durable.
In - line direct injection fuel system: More complete combustion under high injection pressure, less energy loss, more powerful power, and strong fuel adaptability.
Holset turbocharger: Equipped with a belt - driven wastegate, with better low - speed response and power.
Integrated design: The number of parts is about 25% less than that of similar products, with a lower failure rate and more convenient maintenance.
Outstanding reliability: The cylinder liner adopts a platform mesh design and a wear - resistant high - tin aluminum piston, which greatly reduces engine oil consumption, enhances durability, and has a longer service life.
Engine part: Engine, fuel tank, air filter, engine oil filter, charger, starting motor.
Generator part: Generator, air circuit breaker.
Control system: LCD display control panel, electronic speed regulator.
Other parts: Water - cooled radiator, steel base, shock absorber.
Optional parts: Muffler, battery, power cable, oil machine, anti - vibration pad.
Environmental Indicator | Parameter | Environmental Indicator | Parameter |
Altitude (m) | ≤1000 | Water quality pH value | 6.5 - 8 |
Fuel standard | 0# light diesel | Relative humidity | ≤60% |
Atmospheric pressure (kPa) | ≥89.9 | Surface salt spray | ≤GB/T2423.16/2 level |
Engine oil standard | CF grade / 15W - 40 | Vibration resistance intensity | Horizontal acceleration 0.2g, vertical acceleration 0.1g |
Inlet air temperature (℃) | ≤40 |
Generator Set Parameter | Value | Generator Set Parameter | Value |
Model | Mobile power station | Transient voltage regulation rate | ≤ - 15% / + 20% |
Machine type number | KC150GF | Steady - state voltage regulation rate | ≤ ± 1% |
Standby power (KW) | 135 | Voltage stabilization time | ≤3sec |
Rated power (KW) | 150 | Voltage deviation | ≤0.5% |
Trailer size (mm) | 3500×1720×2800 | Voltage waveform distortion degree | ≤8% |
Weight (kg) | 3740 | Steady - state frequency regulation rate | ≤5% |
Rotational speed (r/min) | 1500 | Transient frequency regulation rate | ≤ - 10% / + 12% |
Fuel consumption (g/kw.h) | 210 | Frequency stabilization time | 3sec |
Noise (LP7m) (dB) | 70 - 85 | Frequency fluctuation | ≤1.5% |
Engine Parameters
Engine Parameter | Value | Engine Parameter | Value |
Engine brand | Cummins | Engine oil capacity (L) | 23.8 |
Manufacturer | Dongfeng Cummins Engine Co., Ltd. (DCEC) | Fuel tank capacity | 123 (only for the engine) |
Engine model | 6CTA8.3 - G2 | Cooling method | Closed water cooling cycle |
Standby power (KW) | 163 | Cooling system | Pump - driven |
Arrangement/Row form | 6 - cylinder/in - line | Speed regulation method | Electronic speed regulation |
Compression ratio | 17.0:1 | Start - up method | DC24V electric start |
Bore×Stroke (mm) | 114×135mm | Air intake method | Turbocharged air - to - air intercooling |
Displacement (L) | 8.3 | Type | Four - stroke |
Oil pressure (kPa) | 276 - 414 | Constant load steady - state fluctuation | ±0.25% |
Engine oil temperature (℃) | ≤121 | Power deviation | ≤ ± 5% |
Generator Parameter | Value | Generator Parameter | Value |
Generator brand | Stamford | Insulation class | H class |
Manufacturer | Stamford Electric Technology (China) Co., Ltd. | Power factor | COSφ = 0.8 lagging |
Generator model number | UCI274F | Voltage drop factor | TIF: ≤50 |
Capacity | 175KVA | Wiring | "Y" - type connection |
Voltage | 400V/230V | Radio interference level | THFz: ≤2% |
Form | Brushless, self - excited, rotating magnetic field | Excitation system | Built - in, automatic voltage regulation |
Winding structure | 2/3 pitch | Compliance standard | GB755, BS5000 Part 2, VDE0530, NEMA MG1 - 22, IEC - 34, GSA C22 - 100, AS1359 |
Executive Standards
Standard | Standard | Standard Type | Standard |
Military standard | GJB 5785 - 2006 | Industry standard | JB/T 10303 - 2001 |
National standard | GB/T 2820 - 2002 | Environmental protection inspection | Noise and exhaust level/waste gas level |
Telecommunications standard | YD/T 502 - 2007 | Quality system certification | YD/T502 |
X
Appointment Experience